Filters
- Cardboard Pleated Filters
- Bag Filter
- Deeb Bed Filters
- Compact Filters
- Ancillaries
- Kitchen Filters
Contact Us
- Unit 5/115 Muller Rd, Hampstead Gardens SA 5086, Australia
- sales@barotec.com.au
- (08) 7113 2242
Barotec : Delivering value and engineered solutions through filtration, your filtration distributor
The Condo Opera OT is a laminar flow ceiling module for operation theatres, designed for unidirectional airflow with H14 filters. Built in modular or single-unit form, it supports room-side filter access and ensures airtight, zero-leak performance. Fully tested and compliant with key standards, it delivers reliable contamination control in critical surgical environments.
| Data | Value |
|---|---|
| Category | Laminar HEPA Ceiling Terminal Module for Operation Theatre |
| Conformity Standards | ASHRAE / ASHE Standard-170; NFS 90-351 |
| Housing Box material | Stainless steel/ Galvanized steel or Mild Steel-Powder Coated. |
| Finish | SS 304/ RAL 9010 or equivalent grade to prevent corrosion |
| Design and Construction | As a single unit or as separate Modular Units. Each separate unit can be bolted together at site as a single unit. The joints are later mechanically sealed to be Leak proof & airtight. |
| Diffuser / Face Guard | Perforated type-SS Diffuser/ G.I or M.S Powder Coated. Fully Removable type or Hinged type. |
| Spigot connection | Lateral or Top spigot |
| Spigot | circular or Rectangular with Flanges |
| Central square or rectangular opening | For Surgical Light provision |
| Filter Installation & Mounting | Filter installed from room side by removing diffuser/ Hanging chains provided for hinged type diffuser. Filter locking using quarter turn locks or quick clamping mechanisms with gasket compression inbuilt. |
| Test port | Single Port per module to measure filter replacement pressure drop at site. |
| Pressure Monitoring | DP switch for signaling filter replacement |
| Hanging Clamps | Fully welded hanging Clamps used for ceiling suspension. |
| Performance Testing | Each Laminar OT module shall be fully leak tested. All welds and penetrations shall be bubble tested for leaks and must meet zero leakage criteria. |
| HEPA Filter | Seamless PU Gasket type or Gel Seal type. Please refer Hepa filter technical catalogue for selection. |
| HEPA Grade as per EN 1822 | H14 |
| Maximum Final pressure drop of filter | 500 Pa |
Designed & Developed with ❤️ by HB Softweb